Application

For balancing hydraulic pressure in heating installations consisting of multiple circuits and pumps. The use of our patented PALL-ring technique enables a better response, returns higher efficiency, decreases total built-in height and shares its de-aeration and dirt separation benefits
FlexBalance Plus hydraulic balancers are supplied with an automatic air vent, a dirt chamber have a connection for a temperature sensor. The sensor can be connected using an immersion pipe (G 1/2").
Conventional VDMA 24770 hydraulic balance.
FlexBalance Plus DN150 and larger: Standard equipped with legs.
 

Technical Data

Connections: Flanged according to EN 1092-1 PN16
Maximum operating pressure: 10.0 bar.

Minimum pressure: 0.2bar

Minimum temperature: -10°C

Maximum operating temperature: 120 °C.

Max % glycol: 50%

Maximum recommended flow velocity:
2,0 m/s primary circuit

1.2 m/s. secondary circuit

External coating: 2 part Epoxy (RAL 3002), > 45µm.

 

Approvals

CE 0045 in according with PED 97/23/EC

 

DN A [mm] B [mm] C [mm] E [mm] H [mm] I [mm]Capacity [kW]Flow [m3/h]
50 400 350 950 88 154 -  100 -   200   5 -  15
65 400 350 950 88 154 -  180 -   330  10 -  17
80 625 470 1265 135 188 -  300 -   450  15 -  30
100 625 470 1265 135 188 -  400 -   770  25 -  55
125 830 635 1767 180 213 -  700 -  1150  35 -  80
150 1040 774 2175 225 237 645 1000 -  1750  55 - 120
200 1400 1000 2895 300 277 825 1500 -  2800  90 - 200
250 1850 1220 3646 400 325 977 2500 -  4500 110 - 350
300 1850 1220 3646 400 369 977 4200 -  6400 150 - 500
350 2325 1580 4525 500 398 1177 6000 -  7700 200 - 600
100 2700 1870 5115 600 432 1285 7000 - 10000 250 - 800
= Sold by pack