Application
For balancing hydraulic pressure in heating installations consisting of multiple circuits and pumps. The use of our patented PALL-ring technique enables a better response, returns higher efficiency, decreases total built-in height and shares its de-aeration and dirt separation benefits
FlexBalance Plus hydraulic balancers are supplied with an automatic air vent, a dirt chamber have a connection for a temperature sensor. The sensor can be connected using an immersion pipe (G 1/2").
Conventional VDMA 24770 hydraulic balance.
FlexBalance Plus DN150 and larger: Standard equipped with legs.
Technical Data
Connections: Flanged according to EN 1092-1 PN16
Maximum operating pressure: 10.0 bar.
Minimum pressure: 0.2bar
Minimum temperature: -10°C
Maximum operating temperature: 120 °C.
Max % glycol: 50%
Maximum recommended flow velocity:
2,0 m/s primary circuit
1.2 m/s. secondary circuit
External coating: 2 part Epoxy (RAL 3002), > 45µm.
Approvals
CE 0045 in according with PED 97/23/EC
DN | A [mm] | B [mm] | C [mm] | E [mm] | H [mm] | I [mm] | Capacity [kW] | Flow [m3/h] |
---|---|---|---|---|---|---|---|---|
50 | 400 | 350 | 950 | 88 | 154 | - | 100 - 200 | 5 - 15 |
65 | 400 | 350 | 950 | 88 | 154 | - | 180 - 330 | 10 - 17 |
80 | 625 | 470 | 1265 | 135 | 188 | - | 300 - 450 | 15 - 30 |
100 | 625 | 470 | 1265 | 135 | 188 | - | 400 - 770 | 25 - 55 |
125 | 830 | 635 | 1767 | 180 | 213 | - | 700 - 1150 | 35 - 80 |
150 | 1040 | 774 | 2175 | 225 | 237 | 645 | 1000 - 1750 | 55 - 120 |
200 | 1400 | 1000 | 2895 | 300 | 277 | 825 | 1500 - 2800 | 90 - 200 |
250 | 1850 | 1220 | 3646 | 400 | 325 | 977 | 2500 - 4500 | 110 - 350 |
300 | 1850 | 1220 | 3646 | 400 | 369 | 977 | 4200 - 6400 | 150 - 500 |
350 | 2325 | 1580 | 4525 | 500 | 398 | 1177 | 6000 - 7700 | 200 - 600 |
100 | 2700 | 1870 | 5115 | 600 | 432 | 1285 | 7000 - 10000 | 250 - 800 |