Application
Ready-to-use bracket for mounting pipes to walls or other building structures.
Installation
When used in combination with sliding elements, a tied rod is absolutely essential for absorbing the forces running along the centre line of the pipe.
For cantilever lengths > 500 mm we recommend the integration of a prop-up.
Technical Data
Anchor load classes
A = 1.5 kN
B = 2.5 kN
C = 3.5 kN
D = 6.0 kN
Restrictions
σzul ≤ 160 N/mm2
fperm ≤ L/150 for L > 450 mm
fperm ≤ 3 mm for L ≤ 450 mm
Material: Steel, HCP.
Type | L [mm] | Wall plate [mm] | b [mm] | Dimensions of elongated hole [mm] |
---|---|---|---|---|
41/41 - 320 | 320 | 134 x 40 x 8 | 100 | 13 x 18 |
41/41 - 570 | 570 | 134 x 40 x 8 | 100 | 13 x 18 |
41/41 - 820 | 820 | 134 x 40 x 8 | 100 | 13 x 18 |
41/62 - 320 | 320 | 134 x 40 x 8 | 100 | 13 x 18 |
41/62 - 570 | 570 | 134 x 40 x 8 | 100 | 13 x 18 |
41/62 - 820 | 820 | 134 x 40 x 8 | 100 | 13 x 18 |
41/41 D | 300 | 160 X 50 X 8 | 120 | 13 X 22 |
41/41 D | 500 | 160 X 50 X 8 | 120 | 13 X 22 |
41/41 D | 600 | 160 X 50 X 8 | 120 | 13 X 22 |
41/41 D | 800 | 160 X 50 X 8 | 120 | 13 X 22 |
41/41 D | 1000 | 160 X 50 X 8 | 120 | 13 X 22 |