Welcome

Cart My cart 0 Items
Download PDF

Application

For fixing pipes up to a nominal diameter of NB50 directly to ceilings made of trapezoidal corrugated sheet according to VdS/FM standards or as single point mounting solution.

In cases where VdS or FM regulations are not applicable or in cases of ventilation systems, larger loads may be fixed via crossbars and by an appropriate number of toggle studs.

By turning the threaded rod, it is possible to make height adjustments. This threaded rod is secured and cannot be unscrewed completely.

The Hypalon washer is weather-resistant and thus a crucial safety factor when sealing the mounting bore.

 

Installation

For the installation hole in the trapezoidal sheet the Hole Saw LS is to be used: Type M8 = LS 22, type TD10 = LS 25

 

Technical Data

Nominal load: 0.8 kN for each fixing point

Note: Permissible carrying capacity of the trapezoidal sheet has to be considered.

Material: Steel, electro-galvanised, gasket elastomer.

TypeSprinkler applicationLenght of grub screw
[mm]
Fitting bore
[mm]
B
[mm]
M 8 x 100 VdS 100 22 14
M 8 x 200 VdS 200 22 14
M 10 x 100 FM 100 25 16
 M 10 x 200 FM 200 25 16

 

Approvals

Types M8 for sprinkler systems according to Vds Standards. VdS: G4780118.

Types TD 10 are approved for sprinkler systems by FM.

= Sold by pack
Type
kg
Pack.
Avail.
Art.Cod.
Price
Q.ty