Application
Universal clamping element for bi-lateral attachment of crossbars for pipe runs, ducts, cable lines and equipment to steel beams.
Installation
Position the Beam Clip with the slit side on the component, the lug has to be positioned on the steel girder. Then insert the appropriate hexagon bolt und tighten it with washer and nut.
Determination of the required screw length Lmin:
Arrangement A
Hexagon bolt with Holding Bracket
M12: Lmin = a + b + 47 [mm]
Arrangement B
Inserted T-Head Bolt HZ
M12: Lmin = b + 53 [mm]
Technical Data
Type | climping range [mm] | B [mm] | L [mm] | D [mm] |
M12 | 1-30 | 44 | 60 | 13 |
Type | Tightening torque MA [Nm] |
Fz permitted per Beam clip [kN] 1) |
Shear force load capacity FV,x per 2 Beam Clips [kN] 2) |
M12 | 85 | 13.8 | 3.2 |
1) The specified data relate to the application of a standard hexagon bolt with strength class 8.8.
2) The specified data relate to the worst case with flange thicknesses 30 mm (M12) or 40 mm (M16) as well as a coefficient of static friction µR = 0.20.
A possibly operating tensile force Fz isn't included.
Material: Steel, HCP