MOUNTING PLATE GPL HCP
Application
Element for fixation to wall, ceiling and floor for installations in M&E services.
Technical Data
Permissible anchor values may restrict the application.
Version / Type | Tension [kN] | Perm. bending moment* [Nm] | Max. lever arm [mm] | Welding method |
---|---|---|---|---|
Stabil M10 | 4.0 | 17.2 | 200 | R |
Stabil M12 | 4.0 | 29.6 | 300 | R |
Stabil M16 | 8.5 | 70.3 | 300 | M |
Stabil R 1/2" | 8.5 | 95.0 | 350 | M |
R = resistance welding
M = fusion welding
* Limitation due to the Mounting Plate or the load capacity of the Threaded Stud or the Threaded Tube.
σperm ≤ 160 N/mm2 fperm < 5 mm
Material: Steel, HCP.
Type | Dimension L x W x Th [mm] | Elongated hole d x a [mm] | Centre distance l [mm] |
---|---|---|---|
Stabil M10 | 120 x 40 x 4 | 11 x 25 | 80 |
Stabil M12 | 120 x 40 x 4 | 11 x 25 | 80 |
Stabil M16 | 120 x 40 x 5 | 11 x 25 | 80 |
Stabil 1/2" | 120 x 40 x 5 | 11 x 25 | 80 |
Code | Name | Weight | Number of pieces | ||
---|---|---|---|---|---|
112684 | M10 | 0.15 | 50 | Information request | |
112685 | M12 | 0.16 | 50 | Information request | |
112686 | M16 | 0.20 | 50 | Information request | |
112683 | 1/2'' | 0.21 | 50 | Information request |